Location:Home >> PRODUCTS >> Mineral Insulated Fire-Resistant Cables

Mineral Insulated Fire-Resistant Cable
Mineral insulated cable image 1
Mineral insulated cable image 2
Mineral insulated cable cross section
Mineral insulated cable image 3
Mineral insulated cable image 4
Mineral insulated cable image 4
FIRE-RESISTANT CABLE

Mineral Insulated Fire-Resistant Cable

Cu / MI / FR Filler / LSZH Tape / Cu Sheath

Designed to maintain uninterrupted power to critical fire-fighting and emergency systems during a fire, including fire pumps, fire lifts, emergency and local lighting, evacuation signage, security monitoring, smoke-control and exhaust systems, standby power supplies and other essential equipment.

950°C / 180 min
Fire Resistance
0.6/1 kV
Rated Voltage
50–100 Years
Service Life
6–10 × D
Bending Radius
Contact Us                PDF Datasheet
DETAIL        TECHNICAL DATA        GET A QUOTE
A

Application

Designed to maintain uninterrupted power to critical fire-fighting and emergency systems during a fire, including fire pumps, fire lifts, emergency and local lighting, evacuation signage, security monitoring, smoke-control and exhaust systems, standby power supplies and other essential equipment. Widely used for main feeders, emergency lighting, emergency equipment and fire-protection systems in high-rise buildings, petrochemical facilities, power plants, metallurgical facilities, shopping centers, theaters, hotels, airports and tunnels. Suitable for Class A fire-protection power circuits requiring mineral-insulated fire-resistant cables and designed to meet the highest non-combustibility classification requirements of GB 31247.
★

Advantages

✓ Excellent Fire Resistance: 950°C / 180 min under direct flame exposure, flame + water spray, and flame + mechanical impact tests
✓ High Overload Capability
✓ Custom Continuous Lengths: Supplied in continuous lengths to match project requirements; customized lengths available
✓ Flexible Installation: Bending radius 6D–20D
✓ Long-Term Performance: 50–100 year service life · Inorganic material system · Long-term stability · Low maintenance

Technical Data

Cable Construction
ConductorCopper Conductor
InsulationMineral Insulation
FillerFlame-Retardant Filler
WrappingLSZH Flame-Retardant Tape
Metal SheathCopper
Sheath ConstructionWelded & Corrugated
Sheath ThicknessIn accordance with GB/T 34926-2017
Corrugation ParametersIn accordance with GB/T 34926-2017
Technical Characteristics
StandardGB/T 13033, GB/T 34926
Max. Operating Temp.90°C
Temperature Range0°C to +90°C
Short-Circuit Temp.250°C
Min. Bending Radius6–10 × D
Fire ResistanceMeets GB/T 19666 requirements
Electrical Characteristics
Rated Voltage0.6/1 kV
Max. System Voltage1.2 kV
Test Voltage3.5 kV / 5 min
Insulation Resistance≥100 MΩ·km

Dimensions

Cross Section
n × mm²
Conductor Diameter
mm
Insulation Thickness
mm
Sheath Thickness
mm
Overall Diameter
mm
Weight
kg/km
Conductor Resistance at 20°C
Ω/km
3×25+1×166.0/4.80.55/0.550.519.01198.70.727
3×50+1×258.4/6.00.65/0.550.524.421820.387
3×70+1×3510.0/7.00.65/0.600.628.22957.40.268
3×95+1×5011.6/8.40.65/0.650.632.03604.20.193
On mobile devices, swipe horizontally to view complete technical parameters.

Get a Quote

Tell us your required cross section, cable length, installation environment and quantity. Our sales team will get back to you shortly.
Contact Us            WhatsApp            Download Datasheet